HRS, Large Capacity, General Purpose Chiller, 400 VAC
HRS high capacity standard chillers offer cooling capacities of 9.5, 14.5 and 20.5 kW. Coolant and refrigeration circuits are included in a compact package. The refrigeration circuit is air cooled by a single large fan, with a low sound level of 70~75 dB(A) depending on capacity. Alternately, facility water cooled versions are also available. Set temperatures are PID controlled, while the system is monitored for 42 alarms. Additional features include a heating function, serial communication, and IPX4 ingress rating for outdoor installation.
- Cooling capacities: 9.5 kW, 15.5 or 20.5 kW
- Temperature range setting: 5 to 35°C
- Temperture stability: ±1.0°C (9.5, 14.5 kW); ±1.0°C (20.4 kW)
- Power supply requirement: 3ph 380~415 VAC 50/60 Hz; 3ph 460~480 VAC 60Hz
- Waterproof specification: IPX4
- Circulating fluid: tap or deionized water or 15% ethylene glycol solution
How to order
Specifications
Model
HRS200-Am-46-mS
Cooling method Air-cooled refrigeration
Refrigerant R410A (HFC)
Refrigerant charge kg 1.65
Control method PID control
Ambient temperature/Altitude
∗
1, 7
°C
Temperature: –5 to 45, Altitude: less than 3000 m
Circulating fluid system
Circulating fluid
∗
1, 2
Tap water, 15% Ethylene glycol aqueous solution, Deionized water
Set temperature range
∗
1
°C
5 to 35
Cooling capacity
∗
3, 7
kW 20.5
Heating capacity
∗
4
kW 5.3
Temperature stability
∗
5
°C ±1
Pump
capacity
Rated flow (Outlet) L/min 45 (0.45 MPa)
Maximum flow rate L/min 130
Maximum pump head m 50
Minimum operating flow rate
∗
6
L/min 25
Tank capacity L 25
Circulating fluid outlet, circulating fluid return port
Rc1 (Symbol F: G1, Symbol N: NPT1)
Tank drain port Rc3/4 (Symbol F: G3/4, Symbol N: NPT3/4)
Automatic
fluid fill
system
(Standard)
Supply side pressure range
MPa 0.2 to 0.5
Supply side fluid temperature
°C
5 to 35
Automatic fluid fill port Rc1/2 (Symbol F: G1/2, Symbol N: NPT1/2)
Overflow port
Rc1 (Symbol F: G1, Symbol N: NPT1)
Fluid contact material
Metal
Stainless steel, Copper (Heat exchanger brazing), Brass, Bronze
Resin PTFE, PU, FKM, EPDM, PVC, NBR, POM, PE, NR
Electrical system
Power supply
3-phase 460 VAC (60 Hz)
Allowable voltage range ±10% (No continuous voltage fluctuation)
Applicable earth leakage
breaker (Standard)
Rated current
A 30
Sensitivity of leak current
mA 30
Rated operating current
∗
5
A 14.2
Rated power consumption
∗
5
kW(kVA)
9.1 (11.4)
Noise level (Front 1 m/Height 1 m)
∗
5
dB(A) 75
Waterproof specification IPX4
Accessories
Alarm code list sticker 1 pc. (English),
Operation Manual (for installation/operation) 1 pc. (English),
Y-strainer (40 meshes) 25A, Barrel nipple 25A,
Anchor bolt fixing brackets 2 pcs. (including 6 M8 bolts)
∗
8
Weight (dry state) kg 214
Thermo-chiller
Air-cooled 460 V Type
Standard Type
How to Order
Option
Nil None
A With caster adjuster-foot
K
∗
1
With fluid fill port
∗1 This is a manual fluid fill port that is
different from the automatic fluid fill
port. Fluid can be supplied manually
into the tank without removing the
side panel. (Fluid can be supplied
manually for models without option K
if the side panel is removed.)
Power supply
46
3-phase 460 VAC (60 Hz)
Pipe thread type
Nil
Rc
F
G (With Rc-G conversion fitting)
N
NPT (With Rc-NPT conversion fitting)
Cooling method
A
Air-cooled refrigeration
Cooling capacity
200
20.5 kW
HRS 200 A
46
S
∗1 When the ambient temperature or circulating fluid
temperature is 10°C or below, refer to "Operation at
low ambient temperature or low circulating fluid tem-
perature" (page 14).
∗2 Use fluid in condition below as the circulating fluid.
Tap water: Standard of The Japan Refrigeration And
Air Conditioning Industry Association (JRA GL-02-
1994)
15% ethylene glycol aqueous solution: Diluted with
clean water, without any additives such as antisep-
tics.
Deionized water: Electric conductivity 1 µS/cm or
higher (Electric resistivity 1 MΩ·cm or lower)
∗3 q Ambient temperature: 32°C, w Circulating fluid:
Tap water, e Circulating fluid temperature: 20°C, r
Circulating fluid flow rate: Rated flow, t Power sup-
ply: 460 VAC
∗4 q Ambient temperature: 32°C, w Circulating fluid:
Tap water, e Circulating fluid flow rate: Rated flow,
r Power supply: 460 VAC
∗5 q Ambient temperature: 32°C, w Circulating fluid:
Tap water, e Circulating fluid temperature: 20°C, r
Load: Same as the cooling capacity, t Circulating
fluid flow rate: Rated flow, y Power supply: 460 VAC,
u Piping length: Shortest
∗6 Fluid flow rate to maintain the cooling capacity. If the
actual flow rate is lower than this, install a bypass
piping.
∗7 If the product is used at altitude of 1000 m or higher,
refer to “Operating Environment/Storage Environ-
ment” (page 13) Item 13 “∗ For altitude of 1000 m or
higher.”
∗8 The anchor bolt fixing brackets (including 6 M8 bolts)
are used for fixing to wooden skids when packaging
the thermo-chiller. No anchor bolt is included.
(Pending for UL Standards)
INFORMATION
HRS200 Series
18-E700
Related Products
Email Part
Email How to Order Page
Products
- Actuators
-
Directional Control Valves
- Directional Control Valves Overview
- Solenoid Valves - 4 & 5 Port
- Solenoid Valves - 3 Port
- Solenoid Valves - Direct Operated
- Industrial Communication
- Air Operated Valves
- Mechanical & Hand Operated Valves
- Safety Pressure Relief Valves
- Solenoid Valves - ISO
- Clean Room Products
- Valve Manifold Configurator
- Airline Equipment
- Air Dryers & Main Line Filters
- Connectors
- Vacuum Products
- Industrial Communication
- Sensors & Switches
- Fluid Process
- Static Control
- Electric Actuators
- Chillers
- Process Gas Equipment
- High Vacuum
- Chemical Handling Equipment
- Secondary Battery